TXISP/CO/500 TXgard-IS+ Toxic Gas Detector, 0-250, 500 ppm CO by Crowcon
TXgard-IS+ is a Intrinsically Safe (I.S.) toxic and oxygen gas detector with local LCD display. A wide choice of sensors is available for use in a variety of applications. TXgard-IS+ is ATEX certified for use in Zone 0,1 or 2 hazardous areas, and also UL and cUL certified for use in Division 1 or 2 hazardous areas.
Flexible output options
- 4-20mA current sink or source
- 2 or 3 wire formats
- Optional relays for alarm and fault
- Works with a wide selection of control panels
- Can be used for switching local alarms
Non-intrusive calibration
- Calibration can be performed locally without the need for hot work permits
- Local display and buttons enable calibration without opening the junction box
- Minimises operational down-time
Wide range of sensors
- Choice of catalytic beads for a wide selection of flammable gases and vapours
- Extensive range of electrochemical sensors for toxic gases and oxygen
- Gas detector tailored to your requirements
Low cost of ownership
- Non-intrusive one man calibration
- Long life sensors
- Simple parts replacement
- Easy to operate and maintain
- Keeps interuption to on-site activity to a minimum
Rugged and reliable
- TXgard Plus and Flamgard Plus are constructed using marine grade aluminium with a stainless steel sensor housing
- TXgard-IS+ is made from tough carbon loaded nylon
- Ingress protection to IP65 as standard
- Proven track record for operation in the harshest environments
Size | 160 x 123 x 92mm (6.3 x 4.8 x 4.5ins) |
Weight | 0.7kg (1.5lbs) |
Enclosure material | Junction box: Carbon loaded nylon Sensor housing: ABD Plastic |
Ingress Protection | IP65 |
Cable entries | 1 x M20 or 1/2" NPT with adaptor |
Power | 8-32Vdc, 4-20mA loop-powered |
Operating temperatures | -20°C to +55°C (-4°F to 131°F) * |
Humidity | 15 to 90% RH non-condensing |
Relays (optional) | N/A |
Display | 2-Line, 16 character LCD |
Calibration method | Via push-buttons |
Electrical output | 2 wire 4-20mA |
Terminals | Suitable for up to 2.5mm2 cable |
Sensor type | Electrochemical |
Repeatability | +/- 2% FSD typically |
Zero drift | +/-2% FSD, 6 months typically |
Response time | Contact Crowcon for a full list of sensor response times |
Hazardous area zones | Zone 0, 1 or 2 Division 1 or 2 (when connected via an isolation device) |
Approvals | Ex II 1 G Exia IIC T4 Ga UL Class I, groups A, B, C and D |
EMC compliance | EN50270, FCC, ICES-003 |
Gas Type | LTEL (ppm) |
STEL (ppm) |
Range Available |
Ammonia (NH3) | 25 |
35 |
50, 100, 1000ppm |
Carbon monoxide (CO) | 30 |
200 |
250, 500ppm |
Chlorine (CL2) | - |
0.5 |
5, 10, 20ppm |
Chlorine dioxide (CLO2) | 0.1 |
0.3 |
1 ppm |
Hydrogen (H2) | - |
- |
2000ppm, 50% LEL, 100% LEL |
Hydrogen cyanide (HCN) | - |
10 (MEL) |
25ppm |
Hydrogen fluoride (HF) | 1.8 |
3 |
10ppm |
Hydrogen sulphide (H2S) | 5 |
10 |
25, 50, 100, 200ppm |
Nitrogen dioxide (NO2) | 1 |
1 |
10ppm |
Ozone (O3) | - |
0.2 |
1ppm |
Oxygen (O2) | - |
- |
25% vol. |
Phosgene (COCl2) | 0.02 |
0.06 |
1ppm |
Phosphine (PH3) | 0.1 |
0.2 |
2ppm |
Sulphur Dioxide (SO2) | 1 |
1 |
10, 20, 30ppm |