C011197 Vortex FP Exd Flameproof Control System, 8 input channels, 4 relay modules by Crowcon
Vortex offers all the flexibility you will need while still being simple to operate. All the day to day operations can be completed via push buttons on the front panel. With up to 12 channels, including up to 3 for fire, Vortex can be customised to meet your site requirements, however complex, without the need for extensive cabling.
Wall Mounted: Vortex
A standalone unit for surface mounting on walls, the display panel shows the fault and alarm levels for all the channels, but the LEDs only light when a hazard or fault is detected. This means the whole system can be checked at a glance. Setting adjustments can be made at the enclosure without the need for additional equipment.
Panel Mounted: Vortex Panel
For fitting into an existing panel or door and offering wide range of PSU and battery options.
19 inch Rack Mounted: Vortex Rack
A flexible option where modules, PSU and batteries can be supplied separately for fitting within an existing 19 inch enclosure, permitting multi-rack systems to be created.
Vortex Flameproof
Vortex flameproof (FP) systems are designed for use in ATEX Zones 1 & 2, with IP66 ingress protection, Unlike many other flameproof systems, all day-to-day operations can be undertaken without opening the enclosure, removing the need for hot work permits.
Vortex FP
With up to 24 relays, the enclosure is capable of accommodating up to 4 intrinsically safe (I.S.) barriers for interfacing with I.S. detectors and alarms.
Vortex FP Compact
Not every location can accommodate a Vortex FP unit, so when space is restricted, Vortex FP Compact is an ideal choice. With up to 16 output relays. Intrinsically safe barriers for interface with I.S. detectors and alarms must be housed in a separate enclosure.
Channels and Display
- 1 to 12 channels (including 3 for fire)
- Each channel has 1 fault level and 3 alarm levels which can be combined in any pattern to trigger up to 32 output relays.
- Can be factory set to your requirements. Then when in situ, can easily be configured to suit your requirements using Vortex PC software.
- Push buttons on front display
- LED display panel lights
- Up to 12 devices can be monitored by reviewing just one control panel - saving time and manpower
- Flexibility built in; initially configured to suit your operational needs, then channels/alarms are easily customised by you if requirements change
- Day to day operations are easily undertaken
- Faults are easily seen and whole system can be checked at a glance
Installation and Maintenance
- Modbus compatibility
- Space within units for access to cable terminals
- Uses industry standard communication links
- Any adjustments are performed electronically
- Separate zones can be individually inhibited
- Modular construction
- No extensive cabling required; cable connections within the unit are easy
- Simple to integrate into existing control systems
- Minimal maintenance – no drift from adjustable potentiometers
- You can work on specific areas without affecting the rest of the system
- Replacement parts if required just plug straight in
Compliance and Reliability
- Validated to IEC 61508 (SIL 1)
- System monitors relays continuously
- Internal battery pack
- Demonstrates system dependability
- Coil faults are identified immediately without input from you
- Power outs are not a problem
- Internal battery pack continuously monitored for charge levels and connection
- System is operational at all times
Vortex |
Vortex Rack/Panel |
Vortex FP |
Vortex FP Compact |
||
Size | 470 x 306 x 170mm (18.5 x 12 x 6.5 ins) |
Rack display: standard 19" 3U |
440 x 640 x 332mm (17.3 x 25 x 13 ins) |
450 x 330 x 289mm (17.6 x 13 x 11.4 ins) |
|
Weight | 12Kg (27lbs) |
Dependant on configuration |
70Kgs (154lbs) approx. |
37.5kgs (83lbs) approx. |
|
Enclosure material | Back-box: Aluminium Front cover: ABS |
Not applicable |
LM25 aluminium with polyester powder coating |
||
Ingress protection | IP65 |
Cabinet dependent |
IP66 |
||
Channels | Up to 12 (1 to 3 4-way input modules) |
||||
Inputs | Gas |
2 or 3 wire 4-20mA (sink or source), 0-5V |
|||
Fire - smoke & heat detectors, manual call-points |
Up to 3 loops, Up to 20 devices per loop |
||||
Outputs | External audible/visual alarm drive |
Via relays, four 24Vdc 0.5A supplies provided. |
|||
Relays | Type |
Up to 24 SPCO, contacts rated 6A @ 250Vac (1 to 3 8-way relay modules) |
Up to 32 SPCO with bus extension module |
Relay limitations: 1 or 2 input modules: 2 relay modules max. (16 relays) 3 input modules: 1 relay module only (8 relays) |
|
Assignment - Common |
Mains fail, battery low, battery fail |
Battery back-up not available |
|||
Assignment - Voting |
Alarms, faults and system events |
||||
Relay modes |
Energised/de-energised, latched/non-latched, time-delayed, pulsed |
||||
Digital communications | DCS/PLC/PC |
RS-485 Modbus or Profibus |
|||
Local configuration link |
RS-232 (configuration software and lead supplied) |
||||
Logging | Up to 300 alarm, power, fault, system events are stored in Non-Volatile Memory |
||||
Panel indication | Channel number |
2-digit 7-segment Green LED |
Indications as per Vortex. Displayed information can be altered and outputs can be inhibited during calibration using a magnetic key |
||
Gas reading |
4-digit 7-segment Red LED |
||||
Measurement units |
% LEL, ppm, % Vol, Fire |
||||
Power |
Green LED |
||||
Battery OK |
Green LED |
||||
Run/hold indication |
Green LED |
||||
Channel test mode |
Flashing Amber LED |
||||
System fault - integrity watchdog |
Amber LED |
||||
Alarm indication | Audible - internal sounder |
Piezo |
|||
Visual - Alarm |
Level 1 & 2, Red LED |
||||
Visual - Fault |
Per channel, Amber LED |
||||
Visual - Inhibit |
Per zone, Amber LED |
||||
Power | AC mains |
110/120V & 220/240Vac (switchable) 50-60hz 3.2A max |
110Vac or 240Vac 3.2A max 150W PSU 20 - 30Vdc |
85 - 264Vac 0.8A max 75W PSU 20 - 30Vdc |
|
DC |
20-30Vdc |
||||
Battery back-up |
2Ah internal |
Battery back-up not available |
|||
Approvals | Low voltage directive |
EN61010-1 |
|||
EMC |
EN50270, FCC, ICES |
||||
Hazardous area |
Not applicable |
ATEX Ex 112G, IECEx optional |
|||
Operating temperature | -10 to +40°C (14 to 104°F) |
||||
Humidity | 0-95% RH non-condensing |
||||
Functional safety | Validated to IEC61508 |